VLAN | Network | Comment | Access |
---|---|---|---|
ITM-GC5 | 10.7.32.1/19 | BMCs Floor 5 | LxGw01 |
ITM-GC6 | 10.7.0.1/19 | BMCx Floor 6 | LxGw01 |
INFRA-GC | 10.7.192.0/19 | PDUs, FRAKOs, Siclimat | LxGw01 |
Siclimat Steuerung
using vncviewer
32 Ampere=7.4 kW
) á 2 groups (A+D,B+E,C+F) with 4 outlets each. Each group can deliver 3.7 kW
.
230 Volt * 3 * 32 Ampere = 22.1kW
(PDRs limit: 280 kW
per rack row > do not deliver =22.1kW * 16
racks = 354 kW
)
Temperature | Warn | Graceful Shutdown | Cut-off |
---|---|---|---|
Batch Nodes | 45°C | 48°C | 50°C |
File Server | 48°C | 53°C | 55°C |
Temperature | Warn | Cut-off |
---|---|---|
Rack door outside | 40°C | 45°C |
Rack door inside | 55°C | 60°C |
Humidity | Warn | Critical |
---|---|---|
Inside/Outside | < 10% | < 8% |
I | Attachment | Action | Size | Date | Who | Comment |
---|---|---|---|---|---|---|
Hausordnung.pdf | manage | 22 K | 2017-11-14 - 15:17 | ThomasRoth | Hausordnung Green IT Cube | |
png | Screenshot-2017-10-20-Temperatur_1Tag_innerer_aeusserer_Kreislauf_Feuchtkugel.png | manage | 95 K | 2017-11-14 - 14:33 | ThomasRoth | Temperatur 1Tag innerer, aeusserer Kreislauf + Feuchtkugel |
png | Screenshot_2017-10-20_overview.png | manage | 97 K | 2017-11-14 - 14:34 | ThomasRoth | Overview Monitoring |