External Interfaces and device
Following interface are already known.
Software
- Beckhoff TwinCat OPC-Server with no PLC, depricated
- Installation
- Install tcat_290_1030.exe, Beckhoff TwinCat System Software , attached below
- Install TcInfosys.exe, Beckhoff TwinCat Documentation, not attached sine it is too large. Please ask HolgerBrand.
- Install TcOpcSvr410.exe, Beckhoff TwinCat OPC Server , Attached below
- Reboot
- Configuration
- Configure your Beckhoff system with the System Manager and activate the configuration
- Do not forget to enable Auto Boot in the TwinCAT System Properties dialog -> System
- Configure the OPC server
- Start TwinCat OPC Configurator
- Select your device in the I/O Devices tree and select the Device tab and specify
- Name
- AutoCfg = 5
- Ads Port = Port of the task as specified in the System Manager
- AdsNetId = 0.0.0.0.0.0
- Save the configuration
- Test the OPC configuration with the TcOpcClient.exe. Do not forget to Login
- TwinCat OPC-Server with PLC
- CAEN OPC-Server
- Connection Parameter Configuration:
- Start CS and select Tools >> DSC Module >> Configure Tags... from the menu
- Select a FOPI tag and double-click
- Under Connection push edit to manipulate the servers update deadband and rate (changing these settings for one tag affects all other tags connected to OPC server);current configuration look under FopiDataLoggingSupervisoryControlModule
- Select Servers >> Server Explorer in the Tag Configuration Editor to monitor all OPC items by directling connecting to the running OPC Server (most easiest way is to use the Wizard --> right-click on CAEN.HVOPCServer)
- ESONE - mbs
- connect to the specific terminal
- Cave
- go to directory "esone_x86-21"
- type "mbs"
- type "@startup"
- Counting House
- go to directory "mbs/esone" (or "mbs/esone/gtbp.. ?? )
- type "mbs"
- type "@start" (or "@start-esone" ?? )
- send some CNAFŽs to test the connection:
- type "ca cn 1 2 0 0"
- Format of the numbers is: Crate, Slot, Address, Command
- Command 0 = Read in the most regular Term
- The device-answer should be Q=1 (operation ok), X=1 (module ok)
Hardware
- Beckhoff busterminals
- Ethernet Bus coupler
- BC9000 with PLC
- could be used to perform emergency actions
- 1 item ordered, delivered
- BK9000 without PLC
- Busterminals
- KL3204, 4 channel, to connect PT100 sensors via 2-wire
- 16 items ordered, delivered
- KL3202, 2 channel, to connect PT100 sensors via 2/3-wire
- KL9400, Netzteilklemme zur K-Bus-Auffrischung
- KL9010, Endklemme
- 1 item ordered, delivered
- CAEN SY1527 HV power supply
- NI GPBI-ENET Gateways
- GpibEnet2.gsi.de
- Agilent E3633A, GPIB-Addr: 1
- Agilent E3633A, GPIB-Addr: 2
- Agilent 6031A, GPIB-Addr: ?
- Gasmixer
--