Configuration of the Data Logging and Supervisory Control Module
Please refer to the Configuration Instruction in
FopiCsComputers
first!
Configuration of the Data Logging and Supervisory Control Module
Documentation:
Configuration
Where to go next?
Documentation:
DSC Module
Getting Started with the LabVIEW Datalogging and Supervisory Control Module
LabVIEW Datalogging and Supervisory Control Module Developer Manual
Configuration
Tag Configuration: F:\FOPI\FOPI.scf
Maximum time between logs: 5 min
CAEN HV Channel mapping: F:\FOPI\configuration Files\Mapping.txt
Includes information how HV channels are mapped to detector sectors and temperature sensors.
default alarm settings for CAEN HV and temperature values: F:\FOPI\FoPi.ini
HI HI and HI are limits to be exceeded to cause an alarm
LO LO and LO are limits to be under - run to cause an alarm
The limits have to be in ascending order from LO LO to HI HI, otherwise the default settings of the specific parameter wonŽt affect the DSCEngine.
A limit initialized with 0 disables the alarm limit. In any other case the alarm limit will be enabled.
CITADEL Database: F:\FOPI\DSC
OPC-Servers
CAEN.HVOPCServer
Connection Parameter:
Update Rate: 1 s
Deadband: 0.01 % of range
TwinCAT OPC Server
Connection Parameter:
Update Rate: 1 s
Deadband: 0.01 % of range
Where to go next?
Continue with
FopiCsConfiguration
.
--
HolgerBrand
- 04 Jul 2005
This topic: CSframework
>
WebHome
>
FopiControlSystem
>
FopiDataLoggingSupervisoryControlModule
Topic revision:
2006-11-28,
HolgerBrand
Copyright © by the contributing authors. All material on this collaboration platform is the property of the contributing authors.
Ideas, requests, problems regarding GSI Wiki?
Send feedback
|
Legal notice
|
Privacy Policy (german)